AC Power Supply ANFC Series

AC Power Supply ANFC Series

    ANFC Series

  The ANFC series AC power supply adopts FPGA digital control, instantaneous waveform control and high-frequency pulse width modulation (SPWM) technologies. It has the advantages of fast response speed, high output accuracy, and superior waveform quality; it can withstand 3 times the rated current impact ,high capacity and strong load adaptability; adopts modular design concept, small volume and weight, convenient operation and high cost performance. Mainly used in applications such as home appliances, motors and production lines, it is one solution that meets the basic needs of traditional industries and a power supply alternative for equipment upgrades.

  Features

  1.Adopt FPGA digital technology, realize accuracy control and high quality sine wave output;

  2.Operating in over current shock (up to 3 times of rated current)within 2s, start the impact load of 1/3 capacity of power supply directly;

  3.Adjustable voltage and frequency during output status;

  4.Three-phase loading separately, start single phase output by U/V/W fast settings;(Only suitable for three-phase output power supply);

  5.Measurement: voltage, current, frequency, active power;

  6.Online monitoring: monitor IGBT temperature, transformer temperature, fan speed, input voltage and other parameters during output status;

  7.Operating data recorders: keep the record of power supply status and alarm code automatically during alarming;

  8.Voltage range: 1.0-150.0V or 150.1-300.0 V automatic adjustment, or locked at 1.0-300.0V;

  9.Shortcuts groups, power-off memory, shortcuts key and knobs operation;

  10.Fan speed will be adjustable automatically with the temperature of power supply to reduce the noise;

  11.Lock key, user-friendly design, automatically locking without operation for 5 minutes to prevent from operation mistakes;

  12.Standard RS232, optional RS485, GPIB, Ethernet, analog control and other remote communication/control.

  Applications

  Over shock capacity: impact load of 1/3 capacity of power supply directly without soft start.

  Adjustable voltage and frequency during output

  Three-phase loading separately(Only suitable for three-phase output power supply)

  PC control software

  Specifications of ANFC Single-phase series

Model ANFC015S(F) ANFC020S(F) ANFC030S(F) ANFC045S(F) ANFC060S(F) ANFC090S(F) ANFC120S(F)
Capacity 15kVA 20kVA 30kVA 45kVA 60kVA 90kVA 120kVA
Input Voltage,Frequency 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz
Output Voltage single -phase 2-wires,Automatic files: (low) 1 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:1.0 〜 300.0V
Frequency 45.0~65.0Hz,100Hz、120Hz、200Hz、240Hz
Rated
current
110V 136.3A 181.8A 272.7A 409.1A 545.4A 818.2A 1090.9A
220V 68.2A 90.9A 136.3A 204.5A 272.7A 409.1A 545.4A
Setting accuracy Voltage Resolution:0.1V;accuracy: 0.2%xreading value +0.2%xfull scale value
Frequency Resolution:0.1Hz;accuracy:0.05%
Testing accuracy Voltage Resolution:0.1V;accuracy: 0.2%xreading value +0.2%xfull scale value
Frequency Resolution:0.1Hz;accuracy:0.05%
current Resolution:0.1A/1A,accuracy:0.3%×reading value+0.3%×full scale value
Power   Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value+0.45%×full scale value
Frequency stability ≤0.02%
Voltage distortion Linear load:THD<1%
Transient recovery time 20ms
Crest factor 1.41±0.1
Source voltage effect ≤1%
Load effect ≤1%
Over power 105%<output≤110%  the output will be stopped within 15s ;110%<output≤200%  the output will be stopped within 5s;
200%<output≤300%   the output will be stopped within 2s ;300%<output  the output will be stopped immediately;
Protection  Input  mode IGBT overheat、 IGBT over current、 Transformer overheat、lack  voltage、   Input  over  voltage、   Output  lack  voltage、Output over voltage、 Output over load、 Output short cirluit、output over current
Function Online adjustment function The output voltage and frequency (45~65Hz)can be adjusted online under status
Memory function Power down memory function, memory last output mode and parameters; Shortcut group 7 groups
Line voltage drop compensation 0.000~0.500Ω
Communication control interface Standard:RS232;Optional:RS485、GPIB、Ethernet、Analog control port
Environment Temperature and humidity 0~40℃;20~90%RH
Dimension W×H×D(mm) 600×1130×1018 700×1330×1218 800×1768×1418
Weight (Kg) 175 190 250 370 500 560 970
 

  Specifications of ANFC Three-phase series

Model ANFC015T(F) ANFC030T(F) ANFC045T(F) ANFC060T(F) ANFC090T(F) ANFC120T(F) ANFC180T(F) ANFC240T(F)
Capacity 15kVA 30kVA 45kVA 60kVA 90kVA 120kVA 180kVA 240kVA
Input Voltage,Frequency 3-phase 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz
Output Voltage Three -phawe 4-wires,Automatic files: (low) 1.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:1.0 〜 300.0V
Frequency 45.0~65.0Hz,100Hz、120Hz、200Hz、240Hz
Rated
current
110V 45.4A 90.9A 136.3A 181.8A 272.7A 363.6A 545.4A 727.2A
220V 22.7A 45.4A 68.2A 90.9A 136.3A 181.8A 272.7A 363.6A
Setting accuracy Voltage Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value
Frequency Resolution:0.1Hz,accuracy:0.05%
Testing accuracy Voltage Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value
Frequency Resolution:0.1Hz,accuracy:0.05%
current Resolution:0.1A/1A,accuracy:0.3%×reading value +0.3%×full scale value
Power   Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value +0.45%×full scale value
Frequency stability ≤0.02%
Voltage distortion Linear load:THD<1%
Transient recovery time 20ms
3 phase phase difference 120°±2°
Crest factor 1.41±0.1
Source voltage effect ≤1%
Load effect ≤1%
Over power 105%<output≤110%  the output will be stopped within 15s ;110%<output≤200%  the output will be stopped within 5s;
200%<output≤300%   the output will be stopped within 2s ;300%<output  the output will be stopped immediately
Protection  Input  mode IGBT overheat、 IGBT over current、 Transformer overheat、lack  voltage、   Input  over  voltage、   Output  lack  voltage、Output over voltage、 Output over load、 Output short cirluit、output over current
Function Online adjustment function The output voltage and frequency (45~65Hz)can be adjusted online under status
Memory function Power down memory function, memory last output mode and parameters; Shortcut group 7 groups
Line voltage drop compensation 0.000~0.500Ω
Communication control interface Standard:RS232;Optional:RS485、GPIB、Ethernet、Analog control port
Environment Temperature and humidity 0~40℃;20~90%RH
Dimension W×H×D(mm) 600×1130×1018 700×1330×1218 800×1768×1418
Weight (Kg) 260 300 430 540 730 970 1240 1390

Model ANFC350T(F) ANFC450T(F) ANFC550T(F) ANFC650T(F) ANFC1000T(F) ANFC1500T(F) ANFC2000T(F)
Capacity 350kVA 450kVA 550kVA 650kVA 1000kVA 1500kVA 2000kVA
Input Voltage,Frequency 3-phawe 4-wires + PE,Phase voltage: 220V±33V, line voltage: 380V±57V,50/60Hz±3Hz
Output Voltage Three -phawe 4-wires,Automatic files: (low) 1.0 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:1.0 〜 300.0V Three -phawe 4-wires,Automatic files: (low) 10 ~ 150.0V, (high-grade) 150.1~300V; high-grade lock:10 〜 300.0V
Frequency 45.0~65.0Hz,100Hz、120Hz、200Hz、240Hz 45.0~65.0Hz
Rated
current
110V 1060A 1363A 1666A 1970A 3030A 4545A 6060A
220V 530.3A 681.8A 833.3A 984.8A 1515A 2272A 3030A
Setting accuracy Voltage Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value Resolution:0.1V,accuracy:0.4%×reading value +0.4%×full scale value
Frequency Resolution:0.1Hz,accuracy:0.05%
Testing accuracy Voltage Resolution:0.1V,accuracy:0.2%×reading value +0.2%×full scale value Resolution:0.1V,accuracy:0.4%×reading value +0.4%×full scale value
Frequency Resolution:0.1Hz,accuracy:0.05%
current Resolution:0.1A/1A,accuracy:0.3%×reading value +0.3%×full scale value Resolution:0.1A/1A,accuracy:0.6%×reading value +0.6%×full scale value
Power   Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.45%×reading value +0.45%×full scale value   Resolution:0.1kW/0.01kW/0.001kW,accuracy:0.9%×reading value +0.9%×full scale value
Frequency stability ≤0.02%
Voltage distortion Linear load:THD<3%
Transient recovery time 20ms
3 phase phase difference 120°±2°
Crest factor 1.41±0.1
Source voltage effect ≤1%
Load effect ≤1%
Over power 105%<output≤110%  the output will be stopped within 15s ;110%<output≤200%  the output will be stopped within 5s;
200%<output≤300%   the output will be stopped within 2s ;300%<output  the output will be stopped immediately
Protection  Input  mode IGBT overheat、 IGBT over current、 Transformer overheat、lack  voltage、   Input  over  voltage、   Output  lack  voltage、Output over voltage、 Output over load、 Output short cirluit、output over current
Function Online adjustment function The output voltage and frequency (45~65Hz)can be adjusted online under status
Memory function Power down memory function, memory last output mode and parameters; Shortcut group 7 groups
Line voltage drop compensation 0.000~0.500Ω
Communication control interface Standard:RS232;Optional:RS485、GPIB、Ethernet、Analog control port
Remote control Analog control port (optional)
Environment Temperature and humidity 0~40℃;20~90%RH
Dimension W×H×D(mm) 1800×2000×1400 2400×2000×1400 4800(1200×4)×2000×1200 - - -
Weight (Kg) 2730 3150 4270 4660 - - -
 