AC withstand voltage insulation testerAN9632X(F)

AC withstand voltage insulation testerAN9632X(F)

    AN9632X(F) /AN9605X(F)/AN9671X(F)/ AN9632M(F)/AN9602M(F)/AN9602X(F)

  Features

  Satisfy CCC, IEC, EN,VDE, BS, UL,JIS standard requirements;

  Voltage ramp up/down, satisfy latest industrial standard requirements;

  Breakdown current upper/lower limit setting, intelligent judgment, sound and light alarm;

  AC 50/60Hz output;

  Over voltage, over current protection, manual test wires compensation;

  VFD display, simple operation;

  Remote, RS232/485 interface;

  Satisfy low voltage distribution industry latest requirements.

  Specification of AN9632X(F) /AN9605X(F)/AN9671X(F)/ AN9632M(F)/AN9602M(F)/AN9602X(F)

Model AN9602X(F) AN9605X(F) AN9632X(F) AN9671X(F)
AC Hippot  Test Rated Output 500VA
AC: 5kV/100mA
100VA (AC: 5kV/20mA)  
Output  Voltage Set and Range 0.2kV~5.00kV AC 100mA, 10V/step 0.2kV~5.00kV AC 20mA, 10V/step  
Output Voltage Resolution/Accuracy 10V, ±(2.5% × setting+ 10V)  
Output Frequency Range 50Hz, 60Hz (Optional)  
Output Waveform Sine waveform, pure resistance, above 200V, distortion <5%  
Upper and Lower Limit Leakage Current Setting Upper 0.1~100.00mA, Lower:0~100.00mA Upper: 0.1~20.00mA, Lower:0~20.00mA  
Leakage Current Measurement Range 0.100~3.499mA/3.50~99.99mA 0.100~3.499mA/3.50~20.0mA  
Leakage Current Accuracy ±(2.5% × reading + 5 counts)  
Ramp-up Time Setting Range/Resolution 1.0~999.9s (0=disable)   0.1s/step ,error ±(0.1%×setting+2counts)  
Test Time Setting Range/Resolution 1.0~999.9s (LLL=continues)   0.1s/step,error ±(0.1%×setting+2counts)  
DUT Abnormal Processing Buzzer alarm, Light alarm  
Test Line Clear to Zero 0~0.500mA, manual clear offset  
Insulation Resistance Test Output Voltage Setting and Measurement Range   100V ~1000V  DC  5V/step
Output Voltage Resolution/Accuracy   1V , ±(3% × setting + 5V)
Test Time Setting Range   1.0~999.9s  0.1s/step (LLL= continues)
Lower limit of Insulation Resistance   1~2000MΩ
Upper limit of Insulation Resistance   0~2000MΩ (0=off)
Insulation Resistance Range   1~2000MΩ, auto switching
Insulation Resistance Accuracy   500~1000V: ±(3% × reading + 8counts) 1~200MΩ;
±(8% × reading+8counts) 200~2000MΩ 
Below 500V: ±(5% × reading+8counts) 1~200MΩ;
±(10% × reading+8 counts) 200~2000MΩ
Interface Function RS232(RS485 optional), Remote control(PLC)
Dimension  W×H×D(mm) 320×110×400


















































Model AN9632M(F) AN9602M(F)
AC Hippot  Test Rated Output 1000VA (AC: 5kV/200mA)
Output  Voltage Set and Range 0.2kV~5.00kV AC  10V/step
Output Voltage Resolution/Accuracy 10V, ±(2.5% × setting+10V)
Output Frequency Range 50Hz, 60Hz (Optional)
Output Waveform Sine waveform, pure resistance load, above 200V, distortion <5%
Upper and Lower Limit Leakage Current Setting 0.10~99.99mA, 0.01mA/step;100.0~200.0mA,0.1mA/step
Leakage Current Measurement Range 0.001~3.499mA/3.50~99.99mA,100.0~199.9mA
Leakage Current Accuracy ±(2.5% × reading + 5 counts)
Ramp-up Time Setting Range/Resolution 1.0~999.9s (0=ramp off)   0.1s/step
Test Time Setting Range/Resolution 1.0~999.9s (LLL=continues)   0.1s/step
(AN9602M(F) 200mA output time:5 minutes)
DUT Abnormal Processing Buzzer alarm, Light alarm
Test Line Clear to Zero 0~0.500mA, manual clear offset
Insulation Resistance Test Output Voltage Setting and Measurement Range 100V ~1000V  DC  5V/step  
Output Voltage Resolution/Accuracy 1V , ±(3% × setting+5V)  
DC ripple factor ≤5%(resistive load measured at 1kV DC, <1mA)  
Test Time Setting Range 1.0~999.9s  0.1s/step (LLL= continues)  
Lower limit of Insulation Resistance 1~2000MΩ  
Upper limit of Insulation Resistance 0~2000MΩ (0=off)  
Insulation Resistance Range 1~2000MΩ, auto switching  
Insulation Resistance Accuracy 500~1000V: ±(3% × reading+8counts) 1~200MΩ;
±(8% × reading+8counts) 200~2000MΩ 
Below 500V: ±(5% × reading+8counts) 1~200MΩ;
±(10% × reading+8 counts) 200~2000MΩ
 
Interface Function RS232(RS485 optional), Remote control(PLC)
Dimension  W×H×D(mm) 320×110×400

Hot selling products
Bidirection Grid Simulation Power Supply
Single-phase AC/DC power meter
Transformer Induction Voltage Analyzer AN
Leakage Current testerAN9620TX(F)/AN9620X